Hydrant Dispenser

 
WhatsApp Image 2016-11-21 at 1.49.27 PM.jpeg
 
 

Pressure Setting

  • 150 psi 

Flow rate and pump unit

  • 1250 LPM

Design approvals

  • EI 1581 5th edition / EI 1583 6th edition
  • NFPA 407

Filtration

  • Filter monitor - horizontal aligned with air eliminator and relief valve

Design specifications

  • Piping stainless steel SS 316 Hydraulic operated lifting platform
  • Three refueling pressure nozzles – one 2 ½” x 15 m on hose reel and two 2 ½” x 3 mon platform
  • One 4” x 7.5 m intake hydrant hose

Sampling features

  • Multiple sampling points with spring loaded ball valves - filter sump, filter inlet, tank sump and filter outlet
  • One unit of in-lined sampling jar for quick sampling during refuelling

Safety features

  • Deadman control 
  • Bonding cable for electrostatic charge
  • Emergency shut down system
  • Multiple points Interlocking systems 
  • Fire extinguishers

Options

  • Extra air reservoir tank
  • Additional Hose end pressure regulators